Features and technical specifications:
- Multifunctional 3-phase Power Meter :-
3 voltage inputs and 3 current transformer-isolated AC inputs for direct connection to power line or via potential and current transformers
True RMS, volts, amps, power, power factor, neutral current, voltage and current unbalance, frequency
Ampere/Volt demand meter
25/50/60/400 Hz measurement capabilities - Real-time Waveform Capture :-
Real-time “scope mode” waveform monitoring capability
Simultaneous 6-channel one-cycle waveform capture at a rate of 64 samples per cycle - Programmable Logical Controller :-
Embedded programmable controller
16 control setpoints; programmable thresholds and delays
Relay output control (see Available Options)
1-cycle response time - Digital I/O :- Optional four, eight or twelve digital inputs with 1-ms scan time; automatic recording of last five digital input change events with time stamps
Optional two or four relay outputs with 1-cycle update time; unlatched, latched, pulse and KYZ operation; energy pulses - Display :-
Easy to read 3-row (2×4 characters + 1×5 characters) bright LED display, adjustable update time and brightness
Auto-scroll option with adjustable page exposition time; auto-return to a default page
LED bar graph showing percent load with respect to user-definable nominal load current - Meter Security :-
Password security for protecting meter setups and accumulated data from unauthorized changes
The following functions are available
- Digital I/O
- Analog outputs
- TOU – Battery-operated clock unit
- Ethernet communication port
- Profibus DP communication port
- RS-232/RS-422/RS-485 communication port
- GPRS communication port
This PLUS Powermeter Series Block PM130 is easily insert in your schematic diagram and connect as you like way.
Digital I/O :-
1. 4DI/2DO module :-
4 dry contact digital inputs (DI) for monitoring external contacts and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
2 electro-mechanical or solid-state relay outputs (RO) for alarms and controls, and for output energy pulses; unlatched, latched and pulse
operations, failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1-
cycle update time.
2. 8DI module :-
8 dry contact digital inputs (DI) for monitoring external contacts and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time. 12DI/4DO module
12 dry contact digital inputs (DI) for monitoring external contacts and receiving pulses from energy, water, and gas meters
Programmable de-bounce time; 1-ms scan time.
4 electro-mechanical relay outputs (RO) for alarms and controls, and for output energy pulses; unlatched, latched and pulse operations,
failsafe operation for alarm notifications; programmable pulse width; direct remote relay control through communications; 1-cycle update
time.
Analog Output :-
4 optically isolated analog outputs with an internal power supply;
Options for 0-20mA, 4-20mA, 0-1mA, and 1mA output; 1-cycle update time.
Additional Communication Port – COM2 :-
A second COM2 communication port can be ordered as an expansion module. COM2 options available:
Ethernet 10/100BaseT port; MODBUS/TCP , DNP3/TCP and IEC 60870-5-104 communications protocols
Profibus DP port
RS-232/RS-422/RS-485 port; MODBUS RTU, DNP3, SATEC ASCII and IEC 60870-5-101 communication protocols;
GPRS communications port
TOU – Battery-Operated Clock Unit :-
The TOU module provides:
A precise clock with battery backup; 6-year clock retention time
4 dry contact digital inputs (DI) for monitoring external contacts and receiving pulses from energy, water and gas meters; programmable
de-bounce time; 1-ms scan time.
Reviews